DNVGL-RU-SHIP-Pt4Ch8 Electrical installations 10.7.1
b) On three-phase, four-wire circuits, the cross-section of the neutral conductor shall be the same as for a
phase conductor up to 16 mm2, and at least 50% of that of a phase conductor for larger cross-sections,
though not larger than 50 mm2
|
|