ABS 4.8.2/5.15.3 Stored Energy for Starting
The stored energy for starting the emergency generator set is to be maintained at all times, as follows:
i) Electrical and hydraulic starting systems are to be maintained from the emergency switchboard.
ii) Compressed air starting systems may be maintained by the main or auxiliary compressed air receivers through a suitable non-return valve or by an emergency air compressor which, if electrically driven, is supplied from the emergency switchboard.
iii) All of these starting, charging and energy storing devices are to be located in the emergency generator space; these devices are not to be used for any purpose other than the operation of the emergency generating set. This does not preclude the supply to the air receiver of the emergency generating set from the main or auxiliary compressed air system through the non-return valve fitted in the emergency generator space. |