SOLAS Chapter 11-2
Regulation 8
Control of smoke spread
3 Release of smoke from machinery spaces
3.1 The provisions of this paragraph shall apply to machinery spaces of category A and, where the
Administration considers it desirable, to other machinery spaces.
3.2 Suitable arrangements shall be made to permit the release of smoke, in the event of fire, from the space to be protected, subject to the provisions of regulation 9.5.2.1 The normal ventilation systems may be acceptable for this purpose.
3.3 Means of control shall be provided for permitting the release of smoke and such controls shall be
located outside the space concerned so that they will not be cut off in the event of fire in the space they serve. |
|