The space where the emergency fire pump and
its power source are installed is not to be directly adjacent
to machinery spaces of category A or to the space
where the main fire pumps are installed. Where this is
not feasible, the division between the rooms is to be
formed by not more than one bulkhead. Recesses have
to be restricted to a minimum, and doors between the
spaces are to be designed as airlocks. The door towards
the machinery space is to be of A-60 standard.
The bulkhead is to be constructed in accordance with
the insulation requirements for control stations
When a single access to the emergency fire pump room
is through another space adjoining a machinery space
of category A or the spaces containing the main fire
pumps, class A-60 boundary is required between that
other space and the machinery space of category A or
the spaces containing the main fire pumps |
|