If the bilge drainage system for cargo space is additional to the system served by pumps in the machinery
space, the capacity of the system shall be not less than 10 m3/h per cargo space served. If the additional system
is a common system, the capacity need not exceed 25 m3/h. The additional bilge system need not be arranged
with redundancy. (SOLAS Reg. II-2/19.3.5.2)
Whenever flammable or toxic liquids are carried, the bilge line into the machinery space shall be isolated
either by fitting a blank flange or by a closed lockable valve to be located in a readily accessible space outside
cargo holds, e.g. in the engine room. (SOLAS Reg. II-2/19.3.5.3) |
|