据我手头的solas(2001)
CHII -2 Construction-fire protection,detetion,extinction
Regulation 5 Fixed gas fire-extinguishing systems
1.13 When the fire-extinguishing medium is stored outside a protected
space, it shall be stored in a room which shall be situated in a safe and readily
accessible position and shall be effectively ventilated to the satisfaction of the
Administration. Any entrance to such a storage room shall preferably be from
the open deck and in any case shall be independent of the protected space
Access doors shall open outwrds, and bulkheads and decks including doors and other means
of closing any opening therein, which form the boundaries between such rooms
and adjoining enclosed spaces shall be gas tight. |
|