为了确保当时为审图中心疏忽,此事在次跟上海审图中心沟通,回复如下:Dear Sirs,
In case cables for emergency light are passing throu areas with high fire risk, it is required to use fire resistant cables. The definition of areas with high fire risk you can find in the GL-Rules I-1-3 Section 12 E 15. Please see here also Fig. 12.5.
At your Emergency light system diagram it is not mentioned in detail, where the cables are passing throu. As long as the cables are not passing throu areas with high fire risk, fire resisting cables are not required (See GL-Rules I-1-3 Section 12 E 15, Fig. 12.5)
As far as can be seen from the Emergency Lighting System Diagram, I can not see any problem.
Hopefully I could help with this answer. In case of furthermore questions, do not hesitate to contact me again.
xxxxxxxxxxxx/ Kind Regards,xxxxxxxxxxxxxxxxAppointed Assessor, Surveyor