Safety and Control System
Liste zur Prüfung des Alarm- und Sicherheitssystems
List for inspection of the alarm- and safety system
Anlass / Occasion: Commissioning
Anlagennr. / Plant-no.: 4381288
Kennwort / Codeword: Dayang DY208
Werknr. / Code-no.: 1110481
Motortyp / Engine type: 7L58/64CD
Abnahme / Classification: GL
Bestätigung / Acknowledgement
Hiermit bestätigen die Teilnehmer die ordnungsgemäße Durchführung der Prüfung /
The participants herewith confirm that the inspection has been duly accomplished:
Datum / date: ______________________
Teilnehmer / participant: Unterschrift / signature:
Commissioning engineer
Customer
Classification
No. Measuring point Supplier Description Setpoint Function Checked
1 1SAH1000 MAN limit value of 1SE1000-3
engine speed 280 Hz / 471 rpm
hyst: -30 rpm
delay: - overspeed alarm
via pulse counter
2 1SZH1000 MAN limit value of 1SE1000-3
engine speed 293 Hz / 492 rpm
hyst: -
delay: - overspeed shutdown
via pulse counter
3 1SZH1002 MAN relay 1 of 1SSZ1002 492 rpm
release value: 21 rpm
no delay overspeed shutdown 1
293 hz
4 2SZH1002 MAN relay 1 of 2SSZ1002 492 rpm
release value: 21 rpm
no delay overspeed shutdown 2
254.5 hz
5 1SAH1004 MAN limit value of 1ST1004
turbocharger speed 97% of max. tc-speed,H
hyst: -2%
delay: 4s alarm
tc speed high
6 1SZH1004 MAN limit value of 1ST1004
turbocharger speed 100% of max. tc-speed,H
hyst: -2%
delay: 4s load reduction request
tc speed high
7 1HOZ1012 MAN push button
local emergency stop closed for stop emergency stop from local control station
8 2HOZ1012 MAN push button
emergency stop from ECR closed for stop emergency stop from ECR
9 3HOZ1012 push button
emergency stop from WH closed for stop emergency stop from WH
10 2HOS1013 push button
override from WH/ECR closed for override override from WH/ECR
11 1TAH1064 MAN limit value of 1-9TE1064
main bearing temp 90°C,H
hyst: -2K
delay: 4s alarm
main bearing temp high
12 2TZH1064 MAN limit value of 1-9TE1064
main bearing temp 95°C,H
hyst: -2K
delay: 4s auto shutdown
main bearing temp high
13 1SSV1070 MAN pneumatic valve start blocking while turning gear engaged
14 1GOS1070 MAN limit switch
turning gear engaged indication and start blocking
15 1PDSH2105 MAN differential pressure switch
lube oil automatic filter 0.6 bar,H pre-alarm at high filter contamination (for automatic backwash filter type 6.61 with 600s delay)
16 1PDAH2105 MAN limit value of 1PDSH2105
lube oil automatic filter see 1PDSH2105
delay: 10s pre-alarm
lube oil automatic filter contamination high
17 2PDSH2105 MAN differential pressure switch
lube oil automatic filter 0.8 bar,H main alarm and load reduction at high filter contamination
18 2PDAH2105 MAN limit value of 2PDSH2105
lube oil automatic filter see 2PDSH2105
delay: 10s main alarm
lube oil automatic filter contamination high
19 1PDZH2105 MAN limit value of 2PDSH2105
lube oil automatic filter see 2PDSH2105
delay: 30 min load reduction request
lube oil automatic filter contamination high
20 1PDSH2106 MAN differential pressure switch
lube oil indicator filter 0.9 bar,H pre-alarm at high filter contamination
21 1PDAH2106 MAN limit value of 1PDSH2106
lube oil indicator filter see 1PDSH2106
delay: 10s pre-alarm
lube oil indicator filter contamination high
22 2PDSH2106 MAN differential pressure switch
lube oil indicator filter 1.2 bar,H main alarm and load reduction at high filter contamination
23 2PDAH2106 MAN limit value of 2PDSH2106
lube oil indicator filter see 2PDSH2106
delay: 10s main alarm
lube oil indicator filter contamination high
24 1PDZH2106 MAN limit value of 2PDSH2106
lube oil indicator filter see 2PDSH2106
delay: 30 min load reduction request
lube oil indicator filter contamination high
25 1PAL2170 MAN limit value of 1PT2170
lube oil pressure engine inlet 2.0 bar,L (n<320 rpm)
2.8 bar,L (n>320 rpm)
hyst: 0.1 bar
delay: 4s alarm
lube oil pressure low
26 3PSL2170 MAN limit value of 1PT2170
lube oil pressure engine inlet 2.2 bar,L (n<320 rpm)
2.8 bar,L (n>320 rpm)
hyst: 0.1 bar start lube oil standby pump
lube oil pressure low
27 2PZL2170 MAN limit value of 2PT2170
lube oil pressure engine inlet 1.7 bar,L (n<320 rpm)
2.5 bar,L (n>320 rpm)
hyst: 0.1 bar
delay: 4s auto shutdown
lube oil pressure low
28 2PSZL2170 MAN pressure switch
lube oil pressure engine inlet 1.5 bar,L
Delay: 5s hardwired auto shutdown
29 1TAH2170 MAN limit value of 1TE2170
lube oil temp engine inlet 60°C,H
hyst: -2K
delay: 2s alarm
lube oil temp high
30 1TZH2170 MAN limit value of 2TE2170
lube oil temp engine inlet 65°C,H
hyst: -2K
delay: 2s load reduction request
lube oil temp high
31 1ESZ2470 MAN group signal
cylinder lubrication disturbance delay: 30 min load reduction request
cylinder lubrication disturbance
32 1PAL2570 MAN limit value of 1PT2570
lube oil pressure turbocharger inlet 1.1 bar,L
hyst: 0.1 bar
delay: 4s alarm
turbocharger lube oil pressure low
33 2PZL2570 MAN limit value of 2PT2570
lube oil pressure turbocharger inlet 0.9 bar,L
hyst: 0.1 bar
delay: 4s auto shutdown
tc lube oil pressure low
34 1TAH2580 MAN limit value of 1TE2580
lube oil temp turbocharger drain 5K above 110%-value at testrun, H
hyst: -2K
delay: 2s alarm
tc lube oil temp high 84°C
35 2TZH2580 MAN limit value of 2TE2580
lube oil temp turbocharger drain 10K above 110%-value at testrun, H
hyst: -2K
delay: 2s auto shutdown
tc lube oil temp high 89°C
36 1TAH2880 MAN limit value of 1-7TE2880
splash oil temp 80°C,H
hyst: -1K
delay: 1.7s alarm
splashoil temp high
37 2TZH2880 MAN limit value of 1-7TE2880
splash oil temp 85°C,H
hyst: -1K
delay: 1.7s auto shutdown
splashoil temp high
38 1TDAH2880 MAN limit value of 1-7TE2880
splash oil temp +2K,H
hyst: -1 K
delay: 1.7s alarm
splashoil temp mean value deviation
39 2TDZH2880 MAN limit value of 1-7TE2880
splash oil temp +3K,H
hyst: -1 K
delay: 1.7s auto shutdown
splashoil temp mean value deviation
40 1PAL2970 gear supplier limit value of 1PT2970
lube oil pressure gear 0.4 bar,L alarm
gearbox lube oil pressure low
41 2PSZL2970 gear supplier pressure switch
lube oil gear 0.2 bar,L
no delay auto shutdown at low pressure
42 1TAH2970 gear supplier limit value of 1TE2970
lube oil temp gearbox inlet 55°C,H
hyst: -2 K
delay: 2s alarm
gearbox lube oil temp inlet high
43 1TZH2970 gear supplier limit value of 2TE2970
lube oil temp gearbox inlet 60°C,H
hyst: -2 K
delay: 2s load reduction request
gearbox lube oil inlet temp high
44 1TAH2980 gear supplier limit value of 1TE2980
thrust bearing temp gearbox 70°C,H
hyst: -2 K
delay: 2s alarm
gearbox thrust bearing temp high
45 1TZH2980 gear supplier limit value of 2TE2980
thrust bearing temp gearbox 75°C,H
hyst: -2 K
delay: 2s load reduction request
gearbox thrust bearing temp high
46 1PAL3170 MAN limit value of 1PT3170
HT-cooling water pressure engine inlet 1.8 bar,L
hyst: 0.1 bar
delay: 4s alarm
HTCW pressure engine inlet low
47 2PZL3170 MAN limit value of 2PT3170
HT-cooling water pressure engine inlet 1.5 bar,L
hyst: 0.1 bar
delay: 4s auto shutdown
HTCW pressure engine inlet low
48 1TAL3170 MAN limit value of 1TE3170
HT-water temp engine inlet 55°C, L
hyst: 5K
delay: 2s alarm
HTCW temp engine inlet low
49 3PSL3170 yard pressure switch HT-cooling water pump pressure
HT-water after control valve 2.0 bar,L start of standby pump
50 1TAH3180 MAN limit value of 1TE3180
HT-water temp engine outlet 95°C,H
hyst: -2K
delay: 2s alarm
HTCW temp engine outlet high
51 1TZH3180 MAN limit value of 2TE3180
HT-water temp engine outlet 98°C,H
hyst: -2K
delay: 2s load reduction request
HTCW temp engine outlet high
51 1PAL3470 MAN limit value of 1PT3470
nozzle cooling water pressure engine inlet 2.8 bar,L
hyst: 0.1 bar
delay: 4s alarm
nozzle CW pressure low
53 1TAH3470 MAN limit value of 1TE3470
nozzle cooling water temp engine inlet 70°C,H
hyst: -2K
delay: 2s alarm
nozzle CW temp high
54 1PAL4170 MAN limit value of 1PT4170
LT-water pressure charge air cooler inlet 1.2 bar,L
hyst: 0.1 bar
delay: 4s alarm
LTCW pressure low
55 1PAL5070 MAN limit value of 1PT5070
fuel pressure engine inlet 4.0 bar,L
hyst: 0.1 bar
delay: 4s alarm
fuel pressure low
56 1TAH5070 MAN limit value of 1TE5070
fuel temp engine inlet 60°C,H: MDO operation
hyst: -2K
delay: 2s alarm
fuel oil temp high
57 1VA5070 yard limit value of 1VC5070
fuel viscosity device 15 cSt,H
9 cSt,L
delay: 2s alarm
fuel viscosity high/low
58 1LSAH5080 MAN level switch
fuel level in leakage fuel oil monitoring tank alarm at high level
59 1TAH6180 MAN limit value of 1TE6180
charge air temp after charge air cooler 65°C, H
hyst: -2 K
delay: 4s alarm
charge air temp high, active in chatco mode only
60 1PA6182 MAN limit value of 1PT6182
cooling air pressure tc inlet delay: 10s alarm
turbine disc cooling air pressure deviation from characteristic curve (tc speed dependent)
61 1TAH6570 MAN limit value of 1-7TE6570
exhaust gas temp after cylinders 500°C,H
hyst: -5 K
delay: 30s alarm
exhaust gas temp after cyl. high
62 1TZH6570 MAN limit value of 1-7TE6570
exhaust gas temp after cylinders 510°C,H
hyst: -5 K
delay: 30s load reduction request
exhaust gas temp after cyl. high
63 1TDAH6570 MAN limit value of 1-7TE6570
exhaust gas temp after cylinders ±40K,H (60-100% load)
±70K,H (15-59% load)
hyst: -2 K
delay: 3 min alarm
exhaust gas temp after cyl. mean value deviation
64 1TDZH6570 MAN limit value of 1-7TE6570
exhaust gas temp after cylinders ±50K,H (60-100% load)
hyst: -2 K
delay: 3 min load reduction request
exhaust gas temp after cyl. mean value deviation
65 1TAH6575 MAN limit value of 1TE6575
exhaust gas temp before tc 570°C,H
hyst: -5 K
delay: 30s alarm
exhaust gas temp before turbocharger high
66 1TZH6575 MAN limit value of 1TE6575
exhaust gas temp before tc 580°C,H
hyst: -5 K
delay: 30s load reduction request
exhaust gas temp before turbocharger high
67 1PAL7170 MAN limit value of 1PT7170
starting air pressure 15 bar,L
hyst: 0.5 bar
delay: 4s alarm
start air pressure low
68 1PAL7180 MAN limit value of 1PT7180
emergency stop air pressure 10 bar,L
hyst: 0.3 bar
delay: 4s alarm
emergency stop air pressure low
69 1PAL7400 MAN limit value of 1PT7400
control air pressure 5.5 bar,L
hyst: 0.3 bar
delay: 4s alarm
control air pressure low
70
1SDA1000 MAN limit value of 1SE1000-3
engine speed 25rpm
Hyst:-
Delay:10s alarm
deviation between speed sensors
71
1SDA1000 MAN limit value of 1SE1000
engine speed 25rpm
hyst:-
delay:10s alarm
deviation between speed sensors
73
1SZ1010 MAN solenoid in governor
for engine stop energised at stop manual stop and auto shutdown
74
1TDA2170 MAN limit value of 1/2TE2170
lube oil temp engine inlet 5K
hyst:-
delay:60s alarm
deviation between temp sensors 1/2TE2170
75
1TDA2580 MAN limit value of 1/2TE2580
lube oil temp turbocharger
drain 5K
hyst:-
delay:60s alarm
deviation between temp sensors 1/2TE2580
76
1TDA3180 MAN limit value of 1/2TE3180
HT-waterl temp engine outlet 5K
hyst:-
delay:60s alarm
deviation between temp sensors 1/2TE3180
7
77 Boiler
Supplier Leakage Economizer delay: 2s Reduce Load
78 Boiler
Supplier Thermal oil Flow low / low delay: 2s Reduce Load |
|