O. Other Spaces
O 100 Storage rooms for explosives
101 Requirements for storage rooms for explosives are described
in Sec.15.
O 200 Paint lockers and flammable liquid lockers
201 Paint lockers and flammable liquid lockers of deck area
4 m2. and more shall be provided with a fire-extinguishing system
enabling the crew to extinguish a fire without entering the
space. Fixed arrangements as specified below may be provided.
1) CO2 - system, designed for 40% of the gross volume of the
space.
2) Water spraying system, designed for minimum 5 l/m2/
min. Water spraying systems may be connected to the vessel’s
main system.
3) Other systems than those mentioned above, as described in
K101 may be accepted.
202 Lockers of deck area less that 4 m2 shall be arranged
with fire extinguishing appliances complying with SOLAS Ch.
II-2/10.6.3.3.
203 Paint lockers shall be effectively ventilated by mechanical
or natural ventilation independent of other spaces.