SOLAS II-2 / Reg. 9.7.5.2
7.5.2.1 Where they pass through accommodation spaces or spaces containing combustible materials, the exhaust ducts from galley ranges shall be constructed of "A" class divisions. Each exhaust duct shall be fitted with:
.1 a grease trap readily removable for cleaning;
.2 a fire damper located in the lower end of the duct;
.3 arrangements, operable from within the galley, for shutting off the exhaust fans; and
.4 fixed means for extinguishing a fire within the duct.
SOLAS II-2 / Reg. 10.6.4
6.4 Deep-fat cooking equipment
Deep-fat cooking equipment shall be fitted with the following:
.1 an automatic or manual extinguishing system tested to an international standard acceptable to the Organization;*
.2 a primary and backup thermostat with an alarm to alert the operator in the event of failure of either thermostat;
.3 arrangements for automatically shutting off the electrical power upon activation of the extinguishing system;
.4 an alarm for indicating operation of the extinguishing system in the galley where the equipment is installed; and
.5 controls for manual operation of the extinguishing system which are clearly labelled for ready use by the crew. |
|