SOLAS II-2 / Reg. 10.3
3.3 Spare charges
3.3.1 Spare charges shall be provided for 100% of the first 10 extinguishers and 50% of the remaining fire extinguishers capable of being recharged on board. Not more than 60 total spare charges are required. Instructions for recharging shall be carried on board.
3.3.2 For fire extinguishers which cannot be recharged onboard, additional portable fire extinguishers of the same quantity, type, capacity and number as determined in paragraph 3.3.1 above shall be provided in lieu of spare charges.
干粉和泡沫等可充的要满足以上3.3.1, CO2 等不可充要满足3.3.2(刚才笔误纠正一下) |
|