KFD2-CRG2-EX1.D  参数表节选:的技术参数  KFD2-SR2-Ex2.W
General specifications
Signal type        Digital Input
Functional safety related parameters
Safety Integrity Level (SIL)        SIL 2
Supply
Connection        Power Rail or terminals 14+, 15-
Rated voltage        19 ... 30 V DC
Ripple        ≤ 10 %
Rated current        ≤ 50 mA
Power dissipation        ≤ 1 W
Power consumption        ≤ 1 W
Input
Connection side        field side
Connection        terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values        acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current        approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis        1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection        breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio        min. 20 ms / min. 20 ms
Output
Connection side        control side
Connection        output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, II        signal, relay
Contact loading        250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load
Minimum switch current        2 mA / 24 V DC
Energized/De-energized delay        approx. 20 ms / approx. 20 ms
Mechanical life        107 switching cycles
Collective error message        Power Rail
Transfer characteristics
Switching frequency        ≤ 10 Hz
Galvanic isolation
Input/Output        reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply        reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply        reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output        reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements        LEDs
Control elements        DIP switch
Configuration        via DIP switches
Labeling        space for labeling at the front
Directive conformity
Electromagnetic compatibility       
Directive 2014/30/EU        EN 61326-1:2013 (industrial locations)
Low voltage       
Directive 2014/35/EU        EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Conformity
Electromagnetic compatibility        NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Degree of protection        IEC 60529:1989+A1:1999+A2:2013
Functional safety        IEC/EN 61508:2010
Input        EN 60947-5-6:2000
Ambient conditions
Ambient temperature        -20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protection        IP20
Connection        screw terminals
Mass        approx. 150 g
Dimensions        20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting        on 35 mm DIN mounting rail acc. to EN 60715:2001