有船被PSCO寫了缺陷沒有Manually operated call points在[size=15.199999809265137px]油漆房
SOLAS II-2R7.7
Manually operated call points complying with the Fire Safety Systems Code shall be installed throughout the
accommodation spaces, service spaces and control stations. One manually operated call point shall be located
at each exit. Manually operated call points shall be readily accessible in the corridors of each deck such that no
part of the corridor is more than 20 m from a manually operated call point.
SOLAS II-2R9.2.2.4
(5) Service spaces (low risk)
Lockers and store-rooms not having provisions for the storage of flammable liquids and having areas
less than 4 m2 and drying rooms and laundries.
(9) Service spaces (high risk)
Galleys, pantries containing cooking appliances, paint and lamp rooms, lockers and store-rooms having
areas of 4 m2 or more, spaces for the storage of flammable liquids, saunas and workshops other than
those forming part of the machinery spaces.
是不是所有service spaces面積超過4米就要裝Manually operated call points?安裝在裏面還是外邊?那麽一條船便很多Manually operated call points?
|
|