SOLAS II-1 Reg.43
1.2 The emergency source of electrical power, associated transforming equipment, if any, transitional source of emergency power, emergency switchboard and emergency lighting switchboard shall be located above the uppermost continuous deck and shall be readily accessible from the open deck. They shall not be located forward of the collision bulkhead, except where permitted by the Administration in exceptional circumstances.
1.3 The location of the emergency source of electrical power, associated transforming equipment, if any, the transitional source of emergency power, the emergency switchboard and the emergency lighting switchboard in relation to the main source of electrical power, associated transforming equipment, if any, and the main switchboard shall be such as to ensure to the satisfaction of the Administration that a fire or other casualty in the space containing the main source of electrical power, associated transforming equipment, if any, and the main switchboard, or in any machinery space of category A will not interfere with the supply, control and distribution of emergency electrical power. As far as practicable the space containing the emergency source of electrical power, associated transforming equipment, if any, the transitional source of emergency electrical power and the emergency switchboard shall not be contiguous to the boundaries of machinery spaces of category A or those spaces containing the main source of electrical power, associated transforming equipment, if any, and the main switchboard.
公约内容比较绕,要求简述如下:
1. 应置于最高连续甲板之上,并应从露天甲板易于到达。
2. 除在例外情况下经主管机关允许外,不应置于防撞舱壁之前。
3. 应尽可能不与A类机器处所或主电源和主配电板等所在处所的限界面相连接,以保证在主电源和主配电板等所在处所或任何A类机器处所发生火灾或其他事故时,不致妨碍应急电源的供电、控制和配电。
|
|