发表于 2011-4-17 18:58
|
显示全部楼层
来自: 中国香港
"...问之,船级社告知去参考SOLAS Regualtion II-2/5.2.2.1和5.2.2.4。..."
2.2.1 Means of control shall be provided for opening and closure of
skylights, closure of openings in funnels which normally allow exhaust
ventilation and closure of ventilator dampers.
2.2.4 The controls required in paragraphs 2.2.1 to 2.2.3 and in regulation
4.2.2.3.4 shall be located outside the space concerned so they will not be cut
off in the event of fire in the space they serve.
Please noted that the "controls" here (in red color above) denote the "operation control". in case fire, as long as we can shut off the louver ouside the firing space (in fire control station) through such "operation control", the system design is accepted.
另,这控制系统所有的部件都必须是防火的。 |
|