图中红线是什么意思??

spec breaks.jpg -->
回复

使用道具 举报

龙船学院
发表于 2013-1-9 14:25 | 显示全部楼层 来自: 中国上海
Spec break:应该是指 与规格书相背离部分;


可拆式绝缘材料。
回复 支持 反对

使用道具 举报

 楼主| 发表于 2013-1-9 14:34 | 显示全部楼层 来自: 新加坡
蓝色中国心 发表于 2013-1-9 14:25
Spec break:应该是指 与规格书相背离部分;

刚刚问老板了
看看老板的回复:

Specification breaks are required in piping systems for transition from high to low pressure, between high and low temperature service (sometimes), and between corrosive and non-corrosive environments. Temperature is also a consideration because it has an effect on material strength and corrosion resistance. When setting specification breaks it is important to look at the complete piping system from source to destination. The specification break must be positioned so that there is no possibility for the lower pressure, lower/higher temperature or less corrosive resistant piping to be exposed to the harsher condition under any circumstance. Situations to consider include; operator or instrument failure, startup/shut down conditions, line plugging due to hydrate formation or water deposition and freezing, Joule-Thompson expansion (sub-cooling) and plugging with corrosion products or dirt. Also, the destination system must be properly protected with appropriately sized relief valves, vents, etc. Methods that are used to protect a lower pressure piping system downstream from the specification break can include:
a. No valves downstream
b. CSO valves downstream, plus a stringent management policy for such valves.
c. Where appropriate, instrument and control valve failure modes that ensure piping system integrity.
d. Tracing and insulation where appropriate to prevent hydrate formation and ice plugs.
e. Frequent inspection where line plugging or corrosion is suspected to be a problem.
f. Thermal expansion reliefs for trapped fluids. Where appropriate, the procedural solutions discussed above can be covered in a note on the P&ID, and ultimately can be addressed in the plant operating procedures.

回复 支持 反对

使用道具 举报

 楼主| 发表于 2013-1-9 14:38 | 显示全部楼层 来自: 新加坡
但是b. CSO valves downstream, plus a stringent management policy for such valves.

那个stringent management policy是什么来的?
回复 支持 反对

使用道具 举报

头像被屏蔽
发表于 2013-1-9 14:44 | 显示全部楼层 来自: 中国浙江杭州
紧急,,,
回复 支持 反对

使用道具 举报

 楼主| 发表于 2013-1-9 14:48 | 显示全部楼层 来自: 新加坡
问到的结果:

关于removable lagging section是说,在做检查的时候,管子的insulation要能够方便的拆卸下来,以便做检查。

关于stringent management policy还是不太明白。谁有过类似经验的,请指教
回复 支持 反对

使用道具 举报

发表于 2013-1-9 14:49 | 显示全部楼层 来自: 中国上海
看来我理解错了 呵呵  不好意思