1、Scallops are not to be used for penetration unless adequately protected.
2、Cables strap to be SUS with PVC sheathing and all power cables to be marked with non ferrous metal bands and control cables marked with cable ferrules in accordance with drawing
3、Emergency power line supply shall be from the emergency generator. 4、A 300 Amp T.P 440/3Ph/60Hz, 3 wire watertight shore supply complete with connection box, circuit breaker and connected to the main switchboard. This should be capable of supplying power backwards from the main bus to another vessel via another breaker. Power meter, phase indicator, wrong phase interlock, under & over-voltage protection, Volt & Amps meters and internal light must be fitted
5、Cables must not pass thru
scallops in stiffeners and brackets
6、All meters to be marked for normal value and upper limit. Mimic diagram with indicators of MCB open/close condition to be provided.
|