CCS原文应该是FSS CODE第9章翻译过来的。
IMO Resolution MSC.311(88) - 2010年
2 Engineering specifications
2.1 General requirements
2.1.1 Any required fixed fire detection and fire alarm system with manually
operated call points shall be capable of immediate operation at all times (this does
not require a backup co***ol panel). Notwithstanding this, particular spaces may be
disconnected, for example, workshops during hot work and ro-ro spaces during on
and off-loading. The means for disconnecting the detectors shall be designed to
automatically restore the system to normal surveillance after a predetermined time
that is appropriate for the operation in question. The space shall be manned or
provided with a fire patrol when detectors required by regulation are disconnected.
Detectors in all other spaces shall remain operational.
下文摘自最原始版本,MSC 98(73) - 2000版
2 Engineering specifications
2.1 General requirements
2.1.1 Any required fixed fire detection and fire alarm system with manually operated call
points shall be capable of immediate operation at all times.
2.1.2 The fixed fire detection and fire alarm system shall not be used for any other purpose,
except that closing of fire doors and similar functions may be permitted at the co***ol panel.
2.1.3 The system and equipment shall be suitably designed to withstand supply voltage
variation and transients, ambient temperature changes, vibration, humidity, shock, impact and
corrosion normally encountered in ships. |