IGC CODE:
8.2.9. Each pressure relief valve installed on a cargo tank should be connected to a venting system which should be so constructed that the discharge of gas will be unimpeded and directed vertically upwards at the exit and so arranged as to minimize the possibility of water or snow entering the vent system. The height of vent exits should not be less than B/3 or 6 m, whichever is the greater, above the weather deck and 6 m above the working area, the fore and aft gangway, deck storage tanks and cargo liquid lines.
8.2.10. Cargo tank pressure relief valve vent exits should be arranged at a distance at least equal to B or 25 m, whichever is less, from the nearest air intake or opening to accommodation spaces, service spaces and co***ol stations, or other gas-safe spaces. For ships less than 90 m in length, smaller distances may be permitted by the Administration. All other vent exits connected to the cargo containment system should be arranged at a distance of at least 10 m from the nearest air intake or opening to accommodation spaces, service spaces and co***ol stations, or other gas-safe spaces.
|